      1=================================
      2Power allocator governor tunables
      3=================================
      4
      5Trip points
      6-----------
      7
      8The governor works optimally with the following two passive trip points:
      9
     101.  "switch on" trip point: temperature above which the governor
     11    control loop starts operating.  This is the first passive trip
     12    point of the thermal zone.
     13
     142.  "desired temperature" trip point: it should be higher than the
     15    "switch on" trip point.  This the target temperature the governor
     16    is controlling for.  This is the last passive trip point of the
     17    thermal zone.
     18
     19PID Controller
     20--------------
     21
     22The power allocator governor implements a
     23Proportional-Integral-Derivative controller (PID controller) with
     24temperature as the control input and power as the controlled output:
     25
     26    P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power
     27
     28where
     29   -  e = desired_temperature - current_temperature
     30   -  err_integral is the sum of previous errors
     31   -  diff_err = e - previous_error
     32
     33It is similar to the one depicted below::
     34
     35				      k_d
     36				       |
     37  current_temp                         |
     38       |                               v
     39       |              +----------+   +---+
     40       |       +----->| diff_err |-->| X |------+
     41       |       |      +----------+   +---+      |
     42       |       |                                |      tdp        actor
     43       |       |                      k_i       |       |  get_requested_power()
     44       |       |                       |        |       |        |     |
     45       |       |                       |        |       |        |     | ...
     46       v       |                       v        v       v        v     v
     47     +---+     |      +-------+      +---+    +---+   +---+   +----------+
     48     | S |-----+----->| sum e |----->| X |--->| S |-->| S |-->|power     |
     49     +---+     |      +-------+      +---+    +---+   +---+   |allocation|
     50       ^       |                                ^             +----------+
     51       |       |                                |                |     |
     52       |       |        +---+                   |                |     |
     53       |       +------->| X |-------------------+                v     v
     54       |                +---+                               granted performance
     55  desired_temperature     ^
     56			  |
     57			  |
     58		      k_po/k_pu
     59
     60Sustainable power
     61-----------------
     62
     63An estimate of the sustainable dissipatable power (in mW) should be
     64provided while registering the thermal zone.  This estimates the
     65sustained power that can be dissipated at the desired control
     66temperature.  This is the maximum sustained power for allocation at
     67the desired maximum temperature.  The actual sustained power can vary
     68for a number of reasons.  The closed loop controller will take care of
     69variations such as environmental conditions, and some factors related
     70to the speed-grade of the silicon.  `sustainable_power` is therefore
     71simply an estimate, and may be tuned to affect the aggressiveness of
     72the thermal ramp. For reference, the sustainable power of a 4" phone
     73is typically 2000mW, while on a 10" tablet is around 4500mW (may vary
     74depending on screen size). It is possible to have the power value
     75expressed in an abstract scale. The sustained power should be aligned
     76to the scale used by the related cooling devices.
     77
     78If you are using device tree, do add it as a property of the
     79thermal-zone.  For example::
     80
     81	thermal-zones {
     82		soc_thermal {
     83			polling-delay = <1000>;
     84			polling-delay-passive = <100>;
     85			sustainable-power = <2500>;
     86			...
     87
     88Instead, if the thermal zone is registered from the platform code, pass a
     89`thermal_zone_params` that has a `sustainable_power`.  If no
     90`thermal_zone_params` were being passed, then something like below
     91will suffice::
     92
     93	static const struct thermal_zone_params tz_params = {
     94		.sustainable_power = 3500,
     95	};
     96
     97and then pass `tz_params` as the 5th parameter to
     98`thermal_zone_device_register()`
     99
    100k_po and k_pu
    101-------------
    102
    103The implementation of the PID controller in the power allocator
    104thermal governor allows the configuration of two proportional term
    105constants: `k_po` and `k_pu`.  `k_po` is the proportional term
    106constant during temperature overshoot periods (current temperature is
    107above "desired temperature" trip point).  Conversely, `k_pu` is the
    108proportional term constant during temperature undershoot periods
    109(current temperature below "desired temperature" trip point).
    110
    111These controls are intended as the primary mechanism for configuring
    112the permitted thermal "ramp" of the system.  For instance, a lower
    113`k_pu` value will provide a slower ramp, at the cost of capping
    114available capacity at a low temperature.  On the other hand, a high
    115value of `k_pu` will result in the governor granting very high power
    116while temperature is low, and may lead to temperature overshooting.
    117
    118The default value for `k_pu` is::
    119
    120    2 * sustainable_power / (desired_temperature - switch_on_temp)
    121
    122This means that at `switch_on_temp` the output of the controller's
    123proportional term will be 2 * `sustainable_power`.  The default value
    124for `k_po` is::
    125
    126    sustainable_power / (desired_temperature - switch_on_temp)
    127
    128Focusing on the proportional and feed forward values of the PID
    129controller equation we have::
    130
    131    P_max = k_p * e + sustainable_power
    132
    133The proportional term is proportional to the difference between the
    134desired temperature and the current one.  When the current temperature
    135is the desired one, then the proportional component is zero and
    136`P_max` = `sustainable_power`.  That is, the system should operate in
    137thermal equilibrium under constant load.  `sustainable_power` is only
    138an estimate, which is the reason for closed-loop control such as this.
    139
    140Expanding `k_pu` we get::
    141
    142    P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) +
    143	sustainable_power
    144
    145where:
    146
    147    - T_set is the desired temperature
    148    - T is the current temperature
    149    - T_on is the switch on temperature
    150
    151When the current temperature is the switch_on temperature, the above
    152formula becomes::
    153
    154    P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) +
    155	sustainable_power = 2 * sustainable_power + sustainable_power =
    156	3 * sustainable_power
    157
    158Therefore, the proportional term alone linearly decreases power from
    1593 * `sustainable_power` to `sustainable_power` as the temperature
    160rises from the switch on temperature to the desired temperature.
    161
    162k_i and integral_cutoff
    163-----------------------
    164
    165`k_i` configures the PID loop's integral term constant.  This term
    166allows the PID controller to compensate for long term drift and for
    167the quantized nature of the output control: cooling devices can't set
    168the exact power that the governor requests.  When the temperature
    169error is below `integral_cutoff`, errors are accumulated in the
    170integral term.  This term is then multiplied by `k_i` and the result
    171added to the output of the controller.  Typically `k_i` is set low (1
    172or 2) and `integral_cutoff` is 0.
    173
    174k_d
    175---
    176
    177`k_d` configures the PID loop's derivative term constant.  It's
    178recommended to leave it as the default: 0.
    179
    180Cooling device power API
    181========================
    182
    183Cooling devices controlled by this governor must supply the additional
    184"power" API in their `cooling_device_ops`.  It consists on three ops:
    185
    1861. ::
    187
    188    int get_requested_power(struct thermal_cooling_device *cdev,
    189			    struct thermal_zone_device *tz, u32 *power);
    190
    191
    192@cdev:
    193	The `struct thermal_cooling_device` pointer
    194@tz:
    195	thermal zone in which we are currently operating
    196@power:
    197	pointer in which to store the calculated power
    198
    199`get_requested_power()` calculates the power requested by the device
    200in milliwatts and stores it in @power .  It should return 0 on
    201success, -E* on failure.  This is currently used by the power
    202allocator governor to calculate how much power to give to each cooling
    203device.
    204
    2052. ::
    206
    207	int state2power(struct thermal_cooling_device *cdev, struct
    208			thermal_zone_device *tz, unsigned long state,
    209			u32 *power);
    210
    211@cdev:
    212	The `struct thermal_cooling_device` pointer
    213@tz:
    214	thermal zone in which we are currently operating
    215@state:
    216	A cooling device state
    217@power:
    218	pointer in which to store the equivalent power
    219
    220Convert cooling device state @state into power consumption in
    221milliwatts and store it in @power.  It should return 0 on success, -E*
    222on failure.  This is currently used by thermal core to calculate the
    223maximum power that an actor can consume.
    224
    2253. ::
    226
    227	int power2state(struct thermal_cooling_device *cdev, u32 power,
    228			unsigned long *state);
    229
    230@cdev:
    231	The `struct thermal_cooling_device` pointer
    232@power:
    233	power in milliwatts
    234@state:
    235	pointer in which to store the resulting state
    236
    237Calculate a cooling device state that would make the device consume at
    238most @power mW and store it in @state.  It should return 0 on success,
    239-E* on failure.  This is currently used by the thermal core to convert
    240a given power set by the power allocator governor to a state that the
    241cooling device can set.  It is a function because this conversion may
    242depend on external factors that may change so this function should the
    243best conversion given "current circumstances".
    244
    245Cooling device weights
    246----------------------
    247
    248Weights are a mechanism to bias the allocation among cooling
    249devices.  They express the relative power efficiency of different
    250cooling devices.  Higher weight can be used to express higher power
    251efficiency.  Weighting is relative such that if each cooling device
    252has a weight of one they are considered equal.  This is particularly
    253useful in heterogeneous systems where two cooling devices may perform
    254the same kind of compute, but with different efficiency.  For example,
    255a system with two different types of processors.
    256
    257If the thermal zone is registered using
    258`thermal_zone_device_register()` (i.e., platform code), then weights
    259are passed as part of the thermal zone's `thermal_bind_parameters`.
    260If the platform is registered using device tree, then they are passed
    261as the `contribution` property of each map in the `cooling-maps` node.
    262
    263Limitations of the power allocator governor
    264===========================================
    265
    266The power allocator governor's PID controller works best if there is a
    267periodic tick.  If you have a driver that calls
    268`thermal_zone_device_update()` (or anything that ends up calling the
    269governor's `throttle()` function) repetitively, the governor response
    270won't be very good.  Note that this is not particular to this
    271governor, step-wise will also misbehave if you call its throttle()
    272faster than the normal thermal framework tick (due to interrupts for
    273example) as it will overreact.
    274
    275Energy Model requirements
    276=========================